HCCM-2100, Heater Cable Control and Monitoring System

 

panel.jpg (15751 bytes) HCCM-2100 is designed to control and monitor the temperature of critical piping system, and also monitor integrity of heater cables used to heat-trace such piping systems.

The system uses patented communication methods via the heater cable, and does not require dedicated communication wiring.  The system is highly reliable, designed with fail-safe control modes, and performs heater cable and sensor diagnostics, and also self-diagnostics.


Total installed system cost is significantly lower than conventional temperature control and heater cable monitoring systems.  The HCCM-2100 has been successfully utilized by New York City Transit Authority and various commercial institutions for the past four years. These systems are UL approved and are specified by major consulting engineers in New York.
 

Design Guide

Operation and Installation Manual

 

Remote Terminal
The RT-2104 Remote communicates pipe temperature, and system integrity status to the NC-2104. The RT-2104 is connected to the heat trace cable with the cable manufacturer's UL/FM Approved splice kit. The RT-2104 Remote terminals are provided in a NEMA-4X enclosure.
rt.jpg (5739 bytes) Input Power:  5W @ 110/220-277 V AC, 50/60 Hz
Ambient:  -10OC to 55OC (14OF to 131OF)
Storage:   -25OC to 70OC (-13OF to 158OF)
Humidity:   0% to 90% (Non-condensing)
Temperature Sensor Input: Resistive temperature sensor
Mouting:   Pipe or Wall
Approvals:   UL for US and Canada
Network Controller
The NC-2104 is a microprocessor-based network controller. Each Network Controller can monitor and control up to four heating circuits by itself, and up to thirty-two (32) heating circuits with addition of the IO-2104 Input/Output Modules.
ncfront.jpg (7186 bytes) Input Power:  5W @ 110/220-277 V AC, 50/60 Hz
Ambient:  -10OC to 55OC (14OF to 131OF)
Storage:   -25OC to 70OC (-13OF to 158OF)
Humidity:   0% to 90% (Non-condensing)
Control Output:  (4) Dry SPDT, 10 A @ 250 V AC
Alarm Output:  (1) Dry SPDT, 10 A @ 250 V AC
Approvals:   UL for US and Canada
IO Expansion Unit
The IO-2104 Expansion Units are microprocessor-based system expansion devicesthat allow up to 28 zones of monitoring and controlto be added to the NC-2104.
iofront.jpg (7186 bytes) Input Power:  5W @ 110/220-277 V AC, 50/60 Hz
Ambient:  -10OC to 55OC (14OF to 131OF)
Storage:   -25OC to 70OC (-13OF to 158OF)
Humidity:   0% to 90% (Non-condensing)
Control Output:  (4) Dry SPDT, 10 A @ 250 V AC
Approvals:   UL for US and Canada

 

Examples
Remote Terminal settings Network Controller settings HCCM-2100 configuration
IO Expansion Unit settings

 



Home |  Overview |  News |  Products |  Services |  Contact  